Signal modules
5.1 SM500 signal module
SIMATIC TDC hardware
System Manual, 08/2017, A5E01114865-AL
117
Integrating analog inputs
Number
4
Version
Differential inputs
Electrical isolation
No
Input voltage range
-10 V to +10 V
Resolution
Depending on the integration time,
e.g. 15 bits for a 4 ms integration time.
Integration time per channel, max
Configurable
Tolerance
Integral linearity error, max.
Gain error, max.
Typical offset error
0.05%
1%
2 LSB (software adjustment)
Input resistance
470 kΩ
Input filter
2 kHz
Reverse polarity protection
Yes, as differential inputs are used
Digital outputs
Number
16
Electrical isolation
No
External power supply
Rated voltage
Perm. area
short-term
Current consumption, max., no load
24 V
20.4 V to 28.8 V
35 V (for max. 0.5 s)
40 mA
Output voltage range
With 0 signal, max.
With 1 signal, min.
3 V
ext. Supply voltage 2.5 V
Output current
With 0 signal, min.
at 1 signal
Rated value
Valid range, max.
-20 µA
50 mA
100 mA
Delay time
100 µs
Switching frequency of outputs
With resistance load, max.
6 kHz
Short-circuit protection to
Ground
External power supply
yes
No
Short-circuit current, max.
250 mA
Total current of outputs (up to 60 °C)
16 x 50 mA
Limiting of inductive cut-off voltages
ext. Supply voltage +1 V
Aotewell Ltd
www.aotewell.com
HongKong|UK|China
sales@aotewell.com
+86-755-8660-6182

Table of Contents