Use the "Identication" function to check whether you are connected with the required
connectivity module.
Procedure
1. Open the "SIDRIVE IQ Cong" application.
2. Select an asset.
3. Tap on the motor symbol in the list entry.
The connectivity module LED ashes. The rmware version is read out and displayed.
7.1.3 Changing the measuring and send cycles
The following intervals are preset in the factory:
• 5 minutes - interval for measuring temperature, vibration, rotational frequency, operating
status
You can change these settings within a specied range.
• 10 minutes - interval to calculate speed, torque and energy consumption
This interval cannot be set, it is dependent on the selected measurement interval. The
calculation interval is three times as long, i.e. 3 minutes, for a measurement interval of 1
minute. The calculation interval is twice as long for measurement intervals 2 and 5 minutes.
The calculation interval is the same length for all other measurement intervals.
• 24 hours - interval for transmission of the stored data to SIDRIVE IQ Fleet
You can change these settings within a specied range of between 1 and 48 hours.
Note
Eects that inuence the battery life
Shorter intervals result in a shorter battery life.
Note
To calculate the bearing status, the measuring cycle must be set to ≳ 5 minutes.
Operation
7.1Operation with Android
SIMOTICS CONNECT 400
Operating Instructions, 04/2023, A5E50161952B AL 115