EasyManua.ls Logo

Siemens SIMOTICS CONNECT 400 - Page 209

Siemens SIMOTICS CONNECT 400
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Wi-Fi Wi-Fi communication module SN8000/8000UFL to transfer measured data to SI‐
DRIVE IQ Fleet using an encrypted HTTPS connection via TLS 1.2 protocol as well as
for 󹪝rmware updates*
IEEE 802.11b/g/n
Frequency: 2400 GHz – 2483.5 GHz
RF output power: 2412 – 2472 MHz: 18.5 dBm (Max. e.i.r.p.)
Range: up to 100 m
* MindSphere synchronization interval adjustable between 1 hour and 48 hours (default: 24hours)
Status information
Diagnostics LEDs (blue) Status information during con󹪝guration
Integrated sensors
Measurement interval Con󹪝gurable between 1 minute and 1 hour
(default value: 5 minutes)
Temperature measurement
Area -40 °C to +85 °C
Resolution 0.03 °C
* Temperature measured at the contact between the connectivity module and mounting plate
Vibration measurement
Physical measurement principle Total vibration V
RMS
3 axes
Area 0.02 - 180 mm/s
Standard measurement: 10Hz to 1.6kHz (sampling rate: 3.3 kHz)
Performance measurement for a daily detailed evaluation of the health status: 10 Hz
to 3.3kHz (sampling rate: 6.6kHz, for measurement intervals≥5min)
Field measurement
Area 0.01 Hz to 300 Hz
Motor stray 󹪝eld
Standards, approvals, certi󹪝cates
See Directives and standards (Page209)
Degree of protection and protection class
Degree of protection according to EN
60529
IP65
Shock resistance according to Class 3M4 Max. 100 m/s² (tested according to Class 3M4)
Ambient conditions
Ambient temperature during operation -40 °C to +80 °C
Ambient temperature during storage /
transport
-20 °C to +40 °C
Relative humidity 5% to 95% (without condensation)
Software
Mobile app for commissioning and con‐
󹪝guration
SIDRIVE IQ Con󹪝g
Android version through the Google Play Store, iOS version through the Apple App‐
Store
Mechanics / material
Material of the housing Industrial plastic Durethan® (polyamide, halogen-free, glass-󹪝ber reinforced), ma‐
terial of the cover seal made of silicone
Material of the mounting bracket Stainless steel
Further information
10.3Technical data
SIMOTICS CONNECT 400
Operating Instructions, 04/2023, A5E50161952B AL 207

Table of Contents

Other manuals for Siemens SIMOTICS CONNECT 400