SINAMICS G130
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
281/528
Output power
at
400V / 500V / 690 V
Rated output current
or
current derating factor
with pulse frequency of
Current derating factor
with pulse frequency of
1.25 kHz 2.0 kHz 2.5 kHz 4.0 kHz 5.0 kHz 7.5 kHz 8.0 kHz
500 V – 600 V 3AC
110 kW 175 A 92 % 87 % 70 % 60 % 40 %
132 kW 215 A 92 % 87 % 70 % 60 % 40 %
160 kW 260 A 92 % 88 % 71 % 60 % 40 %
200 kW 330 A 89 % 82 % 65 % 55 % 40 %
250 kW 410 A 89 % 82 % 65 % 55 % 35 %
315 kW 465 A 92 % 87 % 67 % 55 % 35 %
400 kW 575 A 91 % 85 % 64 % 50 % 35 %
500 kW 735 A 87 % 79 % 64 % 55 % 25 %
560 kW 810 A 83 % 72 % 61 % 55 % 35 %
660 V – 690 V 3AC
75 kW 85 A 93 % 89 % 71 % 60 % 40 %
90 kW 100 A 92 % 88 % 71 % 60 % 40 %
110 kW 120 A 92 % 88 % 71 % 60 % 40 %
132 kW 150 A 90 % 84 % 66 % 55 % 35 %
160 kW 175 A 92 % 87 % 70 % 60 % 40 %
200 kW 215 A 92 % 87 % 70 % 60 % 40 %
250 kW 260 A 92 % 88 % 71 % 60 % 40 %
315 kW 330 A 89 % 82 % 65 % 55 % 40 %
400 kW 410 A 89 % 82 % 65 % 55 % 35 %
450 kW 465 A 92 % 87 % 67 % 55 % 35 %
560 kW 575 A 91 % 85 % 64 % 50 % 35 %
710 kW 735 A 87 % 79 % 64 % 55 % 25 %
800 kW 810 A 83 % 72 % 61 % 55 % 35 %
SINAMICS G130: Permissible output current (current derating factor) as a function of pulse frequency (continued)
Pulse frequency Maximum attainable output frequency (rounded numerical values)
1.25 kHz 100 Hz
2.00 kHz 160 Hz
2.50 kHz 200 Hz
4.00 kHz 300 Hz
Maximum attainable output frequency as a function of pulse frequency
in operation with factory-set current controller clock cycles
Permissible output current as a function of ambient temperature
SINAMICS G130 converters and associated system components are rated for an ambient temperature of 40 C and
installation altitudes of up to 2000 m above sea level. The output current of SINAMICS G130 converters must be
reduced (current derating) if they are operated at ambient temperatures above 40 C. SINAMICS G130 chassis units
are not permitted to operate at ambient temperatures in excess of 55 C. The following table specifies the permissible
output current as a function of ambient temperature.
Installation altitude
above sea level
Current derating factor
at an ambient temperature (inlet air) of
m 20 °C 25 °C 30 °C 35 °C 40 °C 45 °C 50 °C 55 °C
0 ... 2000 100 % 93.3 % 86.7 % 80.0 %
Current derating factors as a function of ambient temperature (inlet air) for SINAMICS G130 converters