SINAMICS G130
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
290/528
Terminal block on the TM31 Terminal Module
Factory setting Comment
-X520 Optocoupler inputs connected to common
potential
DI0 Not assigned
DI1 Not assigned
DI2 Not assigned
DI3 Acknowledge fault
-X530 Optocoupler inputs connected to common
potential
DI4 OFF 2
1)
Immediate pulse disable, motor coasts to standstill
DI5 OFF 3
1)
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module
DI6 External fault
1)
DI7 Not assigned
-X541 Bidirectional inputs/outputs
DI/DO8 Message: Ready to start
DI/DO9 Not assigned Factory-set as input
DI/DO10 Not assigned Factory-set as input
DI/DO11 External alarm
1)
Factory-set as input
-X542 Relay outputs (changeover contact)
DO0 Inverter enable (Run)
DO1 Checkback signal No converter fault
-X521 Analog inputs, differential
AI0+ Not assigned
AI0-
AI1+ Not assigned
AI1-
-X522 Analog outputs
AO 0V+ The factory setting for the outputs is 0 to 10 V.
AO 0- Analog output, actual speed value
AO 0C+
AO 1V+ The factory setting for the outputs is 0 to 10 V.
AO 1- Analog output, actual motor current value
AO 1C+
-X522 Thermistor protection
+Temp Input for KTY84 or PT1000 temperature sensor or PTC
thermistor
-Temp
The factory settings of the bidirectional inputs/outputs are underscored.
1)
A jumper must be inserted here if these inputs are not used