Loading...
SINAMICS S120 Cabinet Modules
Engineering Information
SINAMICS Engineering Manual – November 2015
Ó Siemens AG
446/528
Motor Modules
The following components require an auxiliary voltage supply:
230 V 1AC: Cabinet ventilation
24 V DC: Open-loop / closed-loop control
Motor Modules Motor Modules
Frame size P
rated
at 400 V
[kW]
230 V 1AC
[A]
24 V DC
[A]
Frame size P
rated
at 690 V
[kW]
230 V 1AC
[A]
24 V DC
[A]
Line supply voltage 380 V to 480 V 3AC Line supply voltage 500 V to 690 V 3AC
HXL 315 0.6 1.5 HXL 450 0.6 1.5
HXL 400 0.6 1.5 HXL 560 0.6 1.5
HXL 450 0.6 1.5 HXL 710 0.6 1.5
JXL 560 0.6 1.5 HXL 800 0.6 1.5
JXL 710 0.6 1.5 JXL 800 0.6 1.5
JXL 800 (1330 A) 0.6 1.5 JXL 1000 0.6 1.5
JXL 800 (1405 A) 0.6 1.5 JXL 1200 0.6 1.5
JXL 1500 0.6 1.5
Heat Exchanger Modules
Heat Exchanger Modules require the 3-phase line voltage to supply the pump and the power supply unit of the
integrated control system (380 V -10 % to 415 V +10 % 3AC / 50 Hz or 660 V -10 % to 690 V +10 % 3AC / 50/60 Hz).
The electronic circuitry of the Heat Exchanger Module can be supplied with 24 V DC either by the internal power
supply unit or the auxiliary voltage supply of the S120 Cabinet Modules (the latter option is recommended).
The following components require an auxiliary voltage supply:
V
Line
3AC: Pump and power supply unit of internal control system
24 V DC: When the internal control system is connected to the
auxiliary voltage supply of the S120 Cabinet Modules
Heat Exchanger Modules Heat Exchanger Modules
Frame size P
rated
at 400 V
[kW]
V
Line
3AC
I
Operation
/ I
Startup
[A] / [A]
24 V DC
[A]
Frame size P
rated
at 690 V
[kW]
V
Line
3AC
I
Operation
/ I
Startup
[A] / [A]
24 V DC
[A]
Line supply voltage 380 V to 415 V 3AC / 50 Hz Line supply voltage 660 V to 690 V 3AC / 50 Hz
- 32 5.5 / 87.7 1.0 - 32 1.8 / 87.7 1.0
- 48 6.2 / 87.7 1.0 - 48 2.2 / 87.7 1.0
- 72 10.9 / 87.7 1.0 - 72 5.2 / 87.7 1.0
- 110 10.9 / 87.7 1.0 - 110 5.2 / 87.7 1.0
Heat Exchanger Modules
Frame size P
rated
at 690 V
[kW]
V
Line
3AC
I
Operation
/ I
Startup
[A] / [A]
24 V DC
[A]
Line supply voltage 660 V to 690 V 3AC / 60 Hz
- 32 2.7 / 87.7 1.0
- 48 3.9 / 87.7 1.0
- 72 4.7 / 87.7 1.0
- 110 4.7 / 87.7 1.0