Parameter Manual
Operating Instructions, 08/2013, 6FC5397-8EP40-0BA0
101
Machine data
2.3 Channel-specific machine data
Description: Event-driven programm calls (Prog-Events) can be set regarding their read-in
disable response.
Bit 0 = 1 :
Prog-Event after start-of-part-program causes block change despite read-in
disable
Bit 1 = 1 :
Prog-Event after end-of-part-program causes block change despite read-in dis-
able
Bit 2 = 1 :
Prog-Event after OP reset causes block change despite read-in disable
Bit 3 = 1 :
Prog-Event after ramp-up causes block change despite read-in disable
Bit 4 = 1 :
Prog-Event after 1st start after search run causes block change despite read-
in disable
Bit 5 = 1 :
Safety-Prog-Event during ramp-up causes block change despite read-in disable
Corresponds to:
MD20105 $MC_PROG_EVENT_IGN_REFP_LOCK
MD20106 $MC_PROG_EVENT_IGN_SINGLEBLOCK
MD20108 $MC_PROG_EVENT_MASK
MD20192 $MC_PROG_EVENT_IGN_PROG_STATE
MD20193 $MC_PROG_EVENT_IGN_STOP
20107 PROG_EVENT_IGN_INHIBIT N01 K1,Z1
- Prog-Events ignore read-in disable DWORD PowerOn
-
- - 0x0C 0 0x3F 2/2