Note
If a connection box is to be operated in "E-stop button evaluated by PROFIsafe" mode, the
connection box cannot be wired according to a hardwired F-system.
Requirement
The connection box standard or advanced is open.
Required number of connecting cables
The wires of the connection cables have been stripped by 8 mm.
Matching ferrules when using 󹪞exible cables
Procedure
1. Connection boxes standard and advanced:
Thread the cables through the corresponding screw glands.
2. When you use 󹪞exible cables, place a wire end ferrule on each wire to be connected.
3. Insert the wire ends into the associated spring-loaded terminal as shown in the 󹪝gures below.
The 󹪝gure below shows the terminals to be connected to the connection box.

Terminal for the emergency stop / stop button
Terminal for the enabling button
4. Connect the cables.
5. For connection box standard and connection box advanced:
When all the required work has been completed in the connection box, close it.
Connecting
4.4 SIMATIC connection box
Handheld Terminal HT 10
Equipment Manual, 09/2020, A5E47430965B AA 49

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SINUMERIK HT 10 and is the answer not in the manual?

Siemens SINUMERIK HT 10 Specifications

General IconGeneral
BrandSiemens
ModelSINUMERIK HT 10
CategoryTouch terminals
LanguageEnglish

Related product manuals