EasyManuals Logo

Siemens SIPROTEC 7RW80 User Manual

Siemens SIPROTEC 7RW80
260 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #108 background imageLoading...
Page #108 background image
Functions
2.9 Jump of Voltage Vector
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
108
Measuring principle
For a three phase voltage connection, the vector of the positive sequence system voltage is calculated . For a
single-phase connection, the connected single-phase voltage is evaluated. The phase angle change of the
voltage vector is determined over a delta interval of 2 cycles. The presence of a phase angle jump indicates an
abrupt change of current flow. The basic principle is shown in Figure 2-32. The diagram on the left shows the
steady state, and the diagram on the right the vector change following a load shedding. The vector jump is
clearly visible.
Figure 2-32 Voltage Vector Following Load Shedding
The function features a number of additional measures to avoid spurious tripping, such as:
Correction of steady-state deviations from rated frequency
Frequency operating range limited to f
N
± 3 Hz
Detection of internal scanning frequency changeover (Scanning frequency adjustment)
Minimum voltage for enabling
Blocking on voltage connection or disconnection
Logic
The logic is shown in Figure 2-33. The phase angle comparison determines the angle difference, and compares
it with the set value. If this value is exceeded, the vector jump is stored in a RS flip-flop. Trippings can be
delayed by the associated time delay.
The stored pickup can be reset via a binary input, or automatically by a timer (address 4604 T RESET).
The vector jump function becomes ineffective on exiting the admissible frequency band. The same applies for
the voltage. In such a case the limiting parameters are V MIN and V MAX.
If the frequency or voltage range is not maintained, the logic generates a logical 1, and the reset input is con-
tinuously active. The result of the vector jump measurement is suppressed. If, for instance, the voltage is con-
nected, and the frequency range is correct, the logical 1 changes to 0. The timer T BLOCK with reset delay
keeps the reset input active for a certain time, thus preventing a pickup caused by the vector jump function.
If a short-circuit causes the voltage to drop abruptly to a low value, the reset input is immediately activated to
block the function. The vector jump function is thus prevented from causing a trip.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7RW80 and is the answer not in the manual?

Siemens SIPROTEC 7RW80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7RW80
CategoryRelays
LanguageEnglish

Related product manuals