Appendix
A.7 Settings
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
230
5588 LR4 after 81-1 Load Restore YES
NO
NO Load restoration element 4 after 81-
1
5589 LR4 after 81-2 Load Restore YES
NO
NO Load restoration element 4 after 81-
2
5590 LR4 after 81-3 Load Restore YES
NO
NO Load restoration element 4 after 81-
3
5591 LR4 after 81-4 Load Restore YES
NO
NO Load restoration element 4 after 81-
4
6101 Synchronizing SYNC function 1 ON
OFF
OFF Synchronizing Function
6102 SyncCB SYNC function 1 (Setting options depend
on configuration)
None Synchronizable circuit breaker
6103 Vmin SYNC function 1 20 .. 125 V 90 V Minimum voltage limit: Vmin
6104 Vmax SYNC function 1 20 .. 140 V 110 V Maximum voltage limit: Vmax
6105 V< SYNC function 1 1 .. 60 V 5 V Threshold V1, V2 without voltage
6106 V> SYNC function 1 20 .. 140 V 80 V Threshold V1, V2 with voltage
6107 SYNC V1<V2> SYNC function 1 YES
NO
NO ON-Command at V1< and V2>
6108 SYNC V1>V2< SYNC function 1 YES
NO
NO ON-Command at V1> and V2<
6109 SYNC V1<V2< SYNC function 1 YES
NO
NO ON-Command at V1< and V2<
6110A Direct CO SYNC function 1 YES
NO
NO Direct ON-Command
6111A TSUP VOLTAGE SYNC function 1 0.00 .. 60.00 sec 0.10 sec Supervision time of V1>;V2> or
V1<;V2<
6112 SYN. DURATION SYNC function 1 0.01 .. 1200.00 sec; 30.00 sec Maximum duration of synchronism-
check
6113A 25 Synchron SYNC function 1 YES
NO
YES Switching at synchronous condition
6121 Balancing V1/V2 SYNC function 1 0.50 .. 2.00 1.00 Balancing factor V1/V2
6122A ANGLE ADJUSTM. SYNC function 1 0 .. 360 ° 0 ° Angle adjustment (transformer)
6123 CONNECTIONof V2 SYNC function 1 A-B
B-C
C-A
A-B Connection of V2
6125 VT Vn2, primary SYNC function 1 0.10 .. 800.00 kV 20.00 kV VT nominal voltage V2, primary
6150 dV SYNCHK V2>V1 SYNC function 1 0.5 .. 50.0 V 5.0 V Maximum voltage difference V2>V1
6151 dV SYNCHK V2<V1 SYNC function 1 0.5 .. 50.0 V 5.0 V Maximum voltage difference V2<V1
6152 df SYNCHK f2>f1 SYNC function 1 0.01 .. 2.00 Hz 0.10 Hz Maximum frequency difference
f2>f1
6153 df SYNCHK f2<f1 SYNC function 1 0.01 .. 2.00 Hz 0.10 Hz Maximum frequency difference
f2<f1
6154 dα SYNCHK α2>α1 SYNC function 1 2 .. 80 ° 10 ° Maximum angle difference
alpha2>alpha1
6155 dα SYNCHK α2<α1 SYNC function 1 2 .. 80 ° 10 ° Maximum angle difference
alpha2<alpha1
8101 MEASURE. SUPERV Measurem.Superv OFF
ON
ON Measurement Supervision
8102 BALANCE V-LIMIT Measurem.Superv 10 .. 100 V 50 V Voltage Threshold for Balance Mon-
itoring
8103 BAL. FACTOR V Measurem.Superv 0.58 .. 0.90 0.75 Balance Factor for Voltage Monitor
8201 FCT 74TC 74TC TripCirc. ON
OFF
ON 74TC TRIP Circuit Supervision
8202 Alarm Delay 74TC TripCirc. 1 .. 30 sec 2 sec Delay Time for alarm
8311 MinMax cycRESET Min/Max meter NO
YES
YES Automatic Cyclic Reset Function
8312 MiMa RESET TIME Min/Max meter 0 .. 1439 min 0 min MinMax Reset Timer
8313 MiMa RESETCYCLE Min/Max meter 1 .. 365 Days 7 Days MinMax Reset Cycle Period
8314 MinMaxRES.START Min/Max meter 1 .. 365 Days 1 Days MinMax Start Reset Cycle in
8315 MeterResolution Energy Standard
Factor 10
Factor 100
Standard Meter resolution
Addr. Parameter Function Setting Options Default Setting Comments