Appendix
A.8 Information List
SIPROTEC, 7RW80, Manual
C53000-G1140-C233-1, Release date 10.2010
234
170.2007 25 Sync. Measuring request of
Control (25 Measu. req.)
SYNC function 1 SP On
Off
*LED
170.2008 >BLOCK 25-group 1 (>BLK 25-1) SYNC function 1 SP On
Off
* LED BI
170.2009 >25 Direct Command output
(>25direct CO)
SYNC function 1 SP On
Off
* LED BI
170.2011 >25 Start of synchronization (>25
Start)
SYNC function 1 SP On
Off
* LED BI
170.2012 >25 Stop of synchronization (>25
Stop)
SYNC function 1 SP On
Off
* LED BI
170.2013 >25 Switch to V1> and V2< (>25
V1>V2<)
SYNC function 1 SP On
Off
* LED BI
170.2014 >25 Switch to V1< and V2> (>25
V1<V2>)
SYNC function 1 SP On
Off
* LED BI
170.2015 >25 Switch to V1< and V2< (>25
V1<V2<)
SYNC function 1 SP On
Off
* LED BI
170.2016 >25 Switch to Sync (>25 synchr.) SYNC function 1 SP On
Off
* LED BI
170.2022 25-group 1: measurement in
progress (25-1 meas.)
SYNC function 1 OUT On
Off
* LED BO 41 203 1 Yes
170.2025 25 Monitoring time exceeded (25
MonTimeExc)
SYNC function 1 OUT On
Off
* LED BO 41 205 1 Yes
170.2026 25 Synchronization conditions
okay (25 Synchron)
SYNC function 1 OUT On
Off
* LED BO 41 206 1 Yes
170.2027 25 Condition V1>V2< fulfilled (25
V1> V2<)
SYNC function 1 OUT On
Off
* LED BO
170.2028 25 Condition V1<V2> fulfilled (25
V1< V2>)
SYNC function 1 OUT On
Off
* LED BO
170.2029 25 Condition V1<V2< fulfilled (25
V1< V2<)
SYNC function 1 OUT On
Off
* LED BO
170.2030 25 Voltage difference (Vdiff) okay
(25 Vdiff ok)
SYNC function 1 OUT On
Off
* LED BO 41 207 1 Yes
170.2031 25 Frequency difference (fdiff)
okay (25 fdiff ok)
SYNC function 1 OUT On
Off
* LED BO 41 208 1 Yes
170.2032 25 Angle difference (alphadiff)
okay (25 αdiff ok)
SYNC function 1 OUT On
Off
* LED BO 41 209 1 Yes
170.2033 25 Frequency f1 > fmax permissi-
ble (25 f1>>)
SYNC function 1 OUT On
Off
* LED BO
170.2034 25 Frequency f1 < fmin permissi-
ble (25 f1<<)
SYNC function 1 OUT On
Off
* LED BO
170.2035 25 Frequency f2 > fmax permissi-
ble (25 f2>>)
SYNC function 1 OUT On
Off
* LED BO
170.2036 25 Frequency f2 < fmin permissi-
ble (25 f2<<)
SYNC function 1 OUT On
Off
* LED BO
170.2037 25 Voltage V1 > Vmax permissi-
ble (25 V1>>)
SYNC function 1 OUT On
Off
* LED BO
170.2038 25 Voltage V1 < Vmin permissible
(25 V1<<)
SYNC function 1 OUT On
Off
* LED BO
170.2039 25 Voltage V2 > Vmax permissi-
ble (25 V2>>)
SYNC function 1 OUT On
Off
* LED BO
170.2040 25 Voltage V2 < Vmin permissible
(25 V2<<)
SYNC function 1 OUT On
Off
* LED BO
170.2090 25 Vdiff too large (V2>V1) (25
V2>V1)
SYNC function 1 OUT On
Off
* LED BO
170.2091 25 Vdiff too large (V2<V1) (25
V2<V1)
SYNC function 1 OUT On
Off
* LED BO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7RW80 and is the answer not in the manual?

Siemens SIPROTEC 7RW80 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7RW80
CategoryRelays
LanguageEnglish

Related product manuals