Introduction
1.3 Characteristics
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
27
Ground Fault Protection 50N, 51N
Three definite time overcurrent protective elements and one inverse time overcurrent protective element for
high-resistance ground faults in grounded systems;
Different curves of common standards are available for 51 and 51N, or a user-defined characteristic;
In-rush restraint with second harmonic oscillation;
Instantaneous tripping by any overcurrent element upon switch onto fault is possible.
Directional Time Overcurrent Protection 67, 67N
Three directional time overcurrent elements for both phase protection and ground protection operate in par-
allel to the non-directional time overcurrent elements. Their pickup values and time delays can be set inde-
pendently from the non-directional time overcurrent elements.
Fault direction with cross-polarized voltages and voltage memory. Dynamically unlimited direction sensitivi-
ty;
Fault direction is calculated phase-selectively and separately for phase faults, ground faults and summation
current faults.
Dynamic Cold Load Pick-up Function 50C, 50NC, 51C, 51NC, 67C, 67NC
Dynamic changeover of time overcurrent protection settings, e.g. when cold load conditions are anticipated;
Detection of cold load condition via circuit breaker position or current threshold;
Activation via automatic reclosure (AR) possible;
Start also possible via binary input.
Single-Phase Overcurrent Protection
Evaluation of the measured current via the sensitive or insensitive ground current transformer;
Suitable as differential protection that includes the neutral point current on a transformer side, a generator
side or a motor side or for a grounded reactor set;
As tank leakage protection against illegal leakage currents between transformer casing and ground.
Voltage Protection 27, 59
Two-element undervoltage detection via the positive sequence system of the voltages, phase-to-phase or
phase-ground voltages;
Choice of current supervision for 27-1 and 27-2;
Two-element overvoltage detection via the positive sequence system voltages, negative sequence system
voltages, phase-to-phase or phase-ground voltages;
For a single-phase connection, the connected single-phase phase-to-ground or phase-to-phase voltage is
evaluated;
settable dropout ratio for all elements of the undervoltage and overvoltage protection.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals