Functions
2.1 General
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
56
2.1.6.2 Setting Notes
Definition of Nominal Rated Values
At addresses 1101 FullScaleVolt. and 1102 FullScaleCurr., the primary reference voltage (phase-
to-phase) and reference current (phase) of the protected equipment is entered (e.g. motors). If these reference
sizes match the primary nominal values of the VTs and CTs, they correspond to the settings in address 202
and 204 (Section 2.1.3.2). They are generally used to show values referenced to full scale.
Ground Impedance Ratios (only for Fault Location)
The adjustment of the ground impedance ratio is only important for the utilization of the line fault location func-
tion. This is done by entering the resistance ratio RE/RL and the reactance ratio XE/XL.
The values under addresses 1103 and 1104 apply if only one line section is available and to all faults that occur
outside the defined line sections.
If several line sections are set, the following shall apply:
for line section 1, addresses 6001 and 6002
for line section 2, addresses 6011 and 6012
for line section 3, the addresses 6021 and 6022.
Resistance ratio RE/RL and reactance ratio XE/XL are calculated formally and do not correspond to the real
and imaginary components of Z
E
/Z
L
. No complex calculation is required! The ratios can be obtained from the
line data using the following formulas:
Where
R
0
– Zero sequence resistance of the line
X
0
– Zero sequence reactance of the line
R
1
– Positive sequence resistance of the line
X
1
– Positive sequence reactance of the line
This data can be used for the entire line or line section, or as distance-related values, since the quotients are
independent of the distance.
Calculation example:
20 kV free line 120 mm
2
with the following data:
R
0
/s = 1.42 /mile Zero resistance
X
0
/s = 2.03 /mile Zero reactance
R
1
/s = 0.39 /km Positive sequence resistance
X
1
/s = 0.55 /km Positive sequence reactance
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals