Siemens SIPROTEC 7SJ62 - Negative Sequence Protection 46-TOC

Siemens SIPROTEC 7SJ62
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Technical Data
4.10 Negative Sequence Protection 46-TOC
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
500
4.10 Negative Sequence Protection 46-TOC
Setting Ranges / Increments
Functional Limit
Trip Time Curves acc. to IEC
Pickup value 46-TOC (I
2p
)for I
Nom
= 1 A 0.10 A to 2.00 A Increments 0.01 A
for I
Nom
= 5 A 0.50 A to 10.00 A
Time Multiplier T
I2p
(IEC) 0.05 s to 3.20 s or (disabled) Increments 0.01 s
Time Multiplier D
I2p
(ANSI) 0.50 s to 15.00 s or (disabled) Increments 0.01 s
Functional Limit for I
Nom
= 1 A all phase currents 10 A
for I
Nom
= 5 A all phase currents 50 A
See also Figure 4-7
The trip times for I
2
/I
2p
20 are identical to those for I
2
/I
2p
= 20.
Pickup Threshold Approx. 1.10· I
2p
www . ElectricalPartManuals . com