Appendix
A.8 Settings
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
646
7151 50N-1 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50N-1
7152 50-2 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50-2
7153 50N-2 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50N-2
7154 51 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 51
7155 51N 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 51N
7156 67-1 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67-1
7157 67N-1 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67N-1
7158 67-2 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67-2
7159 67N-2 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67N-2
7160 67 TOC 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67 TOC
7161 67N TOC 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 67N TOC
7162 sens Ground Flt 79M Auto Recl. No influence
Starts 79
Stops 79
No influence (Sensitive) Ground Fault
7163 46 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 46
7164 BINARY INPUT 79M Auto Recl. No influence
Starts 79
Stops 79
No influence Binary Input
7165 3Pol.PICKUP BLK 79M Auto Recl. YES
NO
NO 3 Pole Pickup blocks 79
7166 50-3 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50-3
7167 50N-3 79M Auto Recl. No influence
Starts 79
Stops 79
No influence 50N-3
7200 bef.1.Cy:50-1 79M Auto Recl. Set value T=T
instant. T=0
blocked T=
Set value T=T before 1. Cycle: 50-1
7201 bef.1.Cy:50N-1 79M Auto Recl. Set value T=T
instant. T=0
blocked T=
Set value T=T before 1. Cycle: 50N-1
7202 bef.1.Cy:50-2 79M Auto Recl. Set value T=T
instant. T=0
blocked T=
Set value T=T before 1. Cycle: 50-2
7203 bef.1.Cy:50N-2 79M Auto Recl. Set value T=T
instant. T=0
blocked T=
Set value T=T before 1. Cycle: 50N-2
7204 bef.1.Cy:51 79M Auto Recl. Set value T=T
instant. T=0
blocked T=
Set value T=T before 1. Cycle: 51
7205 bef.1.Cy:51N 79M Auto Recl. Set value T=T
instant. T=0
blocked T=
Set value T=T before 1. Cycle: 51N
Addr. Parameter Function C Setting Options Default Setting Comments