Appendix
A.9 Information List
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
655
- >CB waiting for Spring charged
(>CB wait)
Process Data SP On
Off
* * LED BI BO CB 101 2 1 Yes
- >No Voltage (Fuse blown) (>No
Volt.)
Process Data SP On
Off
* * LED BI BO CB 160 38 1 Yes
- >Error Motor Voltage (>Err Mot
V)
Process Data SP On
Off
* * LED BI BO CB 240 181 1 Yes
- >Error Control Voltage (>ErrCntr-
lV)
Process Data SP On
Off
* * LED BI BO CB 240 182 1 Yes
- >SF6-Loss (>SF6-Loss) Process Data SP On
Off
* * LED BI BO CB 240 183 1 Yes
- >Error Meter (>Err Meter) Process Data SP On
Off
* * LED BI BO CB 240 184 1 Yes
- >Transformer Temperature (>Tx
Temp .)
Process Data SP On
Off
* * LED BI BO CB 240 185 1 Yes
- >Transformer Danger (>Tx
Danger)
Process Data SP On
Off
* * LED BI BO CB 240 186 1 Yes
- Reset Minimum and Maximum
counter (ResMinMax)
Min/Max meter IntSP
_Ev
ON
- Reset meter (Meter res) Energy IntSP
_Ev
ON BI
- Error Systeminterface (SysIn-
tErr.)
Protocol IntSP On
Off
** LED BO
- Threshold Value 1 (ThreshVal1) Thresh.-Switch IntSP On
Off
LED FC
TN
BO CB
1 No Function configured (Not con-
figured)
Device, General SP * *
2 Function Not Available (Non Exis-
tent)
Device, General SP * *
3 >Synchronize Internal Real Time
Clock (>Time Synch)
Device, General SP_E
v
* * LED BI BO 135 48 1 Yes
4 >Trigger Waveform Capture
(>Trig.Wave.Cap.)
Osc. Fault Rec. SP * * m LED BI BO 135 49 1 Yes
5 >Reset LED (>Reset LED) Device, General SP * * * LED BI BO 135 50 1 Yes
7 >Setting Group Select Bit 0 (>Set
Group Bit0)
Change Group SP * * * LED BI BO 135 51 1 Yes
8 >Setting Group Select Bit 1 (>Set
Group Bit1)
Change Group SP * * * LED BI BO 135 52 1 Yes
009.0100 Failure EN100 Modul (Failure
Modul)
EN100-Modul 1 IntSP On
Off
**LEDBO
009.0101 Failure EN100 Link Channel 1
(Ch1) (Fail Ch1)
EN100-Modul 1 IntSP On
Off
**LEDBO
009.0102 Failure EN100 Link Channel 2
(Ch2) (Fail Ch2)
EN100-Modul 1 IntSP On
Off
**LEDBO
15 >Test mode (>Test mode) Device, General SP * * * LED BI BO 135 53 1 Yes
16 >Stop data transmission
(>DataStop)
Device, General SP * * * LED BI BO 135 54 1 Yes
51 Device is Operational and Pro-
tecting (Device OK)
Device, General OUT On
Off
* * LED BO 135 81 1 Yes
52 At Least 1 Protection Funct. is
Active (ProtActive)
Device, General IntSP On
Of
f
* * LED BO 160 18 1 Yes
55 Reset Device (Reset Device) Device, General OUT on * * 160 4 1 No
56 Initial Start of Device (Initial Start) Device, General OUT on * * LED BO 160 5 1 No
67 Resume (Resume) Device, General OUT on * * LED BO
68 Clock Synchronization Error
(Clock SyncError)
Device, General OUT On
Off
**LEDBO
No. Description Function Type
of In-
for-
matio
n
Log Buffers Configurable in Matrix IEC 60870-5-103
Event Log ON/OFF
Trip (Fault) Log ON/OFF
Ground Fault Log ON/OFF
Marked in Oscill. Record
LED
Binary Input
Function Key
Relay
Chatter Suppression
Type
Information Number
Data Unit
General Interrogation
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals