EasyManuals Logo

Siemens SIPROTEC 7SJ62 User Manual

Siemens SIPROTEC 7SJ62
704 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #85 background imageLoading...
Page #85 background image
Functions
2.2 Overcurrent Protection 50, 51, 50N, 51N
SIPROTEC, 7SJ62/64, Manual
C53000-G1140-C207-2, Release date 01.2008
85
50-1 Element (phases)
For setting the 50-1 element, it is the maximum anticipated load current that must be considered above all.
Pickup due to overload should never occur since in this mode the device operates as fault protection with cor-
respondingly short tripping times and not as overload protection. For this reason, a setting equal to 20% of the
expected peak load is recommended for line protection, and a setting equal to 40% is recommended for trans-
formers and motors.
The settable time delay (address 1205 50-1 DELAY) results from the grading coordination chart defined for
the system.
The selected time is an additional delay time and does not include the operating time (measuring time, dropout
time). The delay can be also be set to . In this case, the element will not trip after pickup. However, pickup,
will be signaled. If the 50-1 element is not required at all, then the pickup threshold 50-1 should be set to .
This setting prevents tripping and the generation of a pickup message.
50N-1 Element (ground)
For setting the 50N-1 ement, it is the minimum anticipated ground fault current that must be considered.
If the relay is used to protect transformers or motors with large inrush currents, the inrush restraint feature of
7SJ62/64 may be used for the 50N–1 relay element. It can be enabled or disabled for both the phase current
and the ground current in address 2201 INRUSH REST.. The characteristic values of the inrush restraint are
listed in Subsection "Inrush Restraint".
The settable delay time (address 1305 50N-1 DELAY) results from the grading coordination chart defined for
the system. For ground currents in a grounded system a separate coordination chart with shorter time delays
is possible.
The selected time is an additional delay time and does not include the operating time (measuring time, dropout
time). The delay can be also be set to . In this case, the element will not trip after pickup. However, pickup,
will be signaled. If the 50N-1 element is not required at all, the pickup threshold 50N-1 PICKUP should be set
to . This setting prevents tripping and the generation of a pickup message.
Pickup Stabilization (Definite Time)
The configurable dropout times 1215 50 T DROP-OUT or 1315 50N T DROP-OUT can be set to implement
a uniform dropout behavior when using electromechanical relays. This is necessary for a time grading. The
dropout time of the electromechanical relay must be known to this end. Subtract the dropout time of the device
(see Technical Data) from this value and enter the result in the parameters.
51 Element (phases) with IEC or ANSI characteristics
Having set address 112 Charac. Phase = TOC IEC or TOC ANSI when configuring the protection functions
(Section 2.1.1.2), the parameters for the inverse characteristics will also be available.
If address 112 Charac. Phase was set to TOC IEC, you can select the desired IEC characteristic (Normal
Inverse, Very Inverse, Extremely Inv.
or Lon
g Inverse) at address 1211 51 IEC CURVE. If
address 112 Charac. Phase was set to TOC ANSI, you can select the desired ANSI characteristic (Very
Inverse, Inverse, Short Inverse, Long Inverse, Moderately Inv., Extremely Inv. or
Definite Inv.) at address 1212 51 ANSI CURVE.
If the inverse time trip characteristic is selected, it must be noted that a safety factor of about 1.1 has already
been included between the pickup value and the setting value. This means that a pickup will only occur if a
current of about 1.1 times the setting value is present. If Disk Emulation was selected at address 1210 51
Drop-out, reset will occur in accordance with the reset curve as described before.
The current value is set in address 1207 51 PICKUP. The setting is mainly determined by the maximum an-
ticipated operating current. Pickup due to overload should never occur since in this mode the device operates
as fault protection with correspondingly short tripping times and not as overload protection.
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens SIPROTEC 7SJ62

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIPROTEC 7SJ62 and is the answer not in the manual?

Siemens SIPROTEC 7SJ62 Specifications

General IconGeneral
BrandSiemens
ModelSIPROTEC 7SJ62
CategoryRelays
LanguageEnglish

Related product manuals