EasyManua.ls Logo

Siemens siprotec 7SJ63 - Page 240

Siemens siprotec 7SJ63
604 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Functions
6-76 7SJ63 Manual
C53000-G1140-C120-1
Implementation In-
structions
In an ungrounded system, the reactive component of the current should be used to
determine the direction. In a grounded system, the real component of the current
should be used to determine the direction. Therefore, in an ungrounded system, ad-
dress  should be set for 6,13+, measurement whereas in a grounded system,
address  should be set for &263+, measurement.
Logic Figure 6-34 illustrates the condition logic for the sensitive ground fault pickup. Ground
fault pickup may be switched 21 or 2)), or into $ODUP2QO\ condition at address
 6HQV*QG)DXOW. When ground fault protection is 21, tripping is possible.
The entire function may be blocked via a binary input. Switching off or blocking means
the measurement logic (shown in Figure 6-35) is deactivated, therefore, time delays
and messages are reset.
Figure 6-34 Activation of Sensitive Ground Fault Detection
or
21
$ODUP2QO\

6HQV*QG)DXOW
“1“
2))
50Ns/67Ns OFF
>BLK 50Ns/67Ns
Sens. Gnd block
&
50Ns/67Ns ACT
F# 1207
F# 1230
F# 1211
F# 1212
Reset Measurement Logic
Alarm Only
to Figure
6-35
www . ElectricalPartManuals . com

Table of Contents

Other manuals for Siemens siprotec 7SJ63

Related product manuals