Configuring
6.3 Operation on failure of the bus connection to the controller
SIRIUS 3RW5 EtherNet/IP communication module
50 Manual, 05/2019, A5E45131885002A/RS-AA/001
More information
The following table describes the assignment of the substitute values "Parameter set bit 0"
and "Parameter set bit 1":
Parameter set
Parameter set bit 0
Parameter set bit 1
Process image error
1
1
Parameter set 1 (PS1) 0 0
Parameter set 2 (PS2)
1
0
Parameter set 3 (PS3) 0 1
Setting options
You can set the parameters in the following ways:
SIRIUS Soft Starter ES (TIA Portal) via local interface on the 3RW5 HMI High Feature
3RW5 HMI High Feature
Menu: "Parameter > Soft Starter > Additional parameters > Operation with CPU / master"
You will find more information on operating the 3RW5 HMI High Feature in the Equipment
Manual of the 3RW5 soft starter.
User program via the Dataset Object "Parameters" (Page 92)