Messages and diagnosis
7.1 LED display
SIRIUS 3RW5 EtherNet/IP communication module
Manual, 05/2019, A5E45131885002A/RS-AA/001
53
7.1.2 Status and error displays
"DIAG" LED
State
Meaning
Lights up green
There is an EtherNet/IP connection between the 3RW5 communication
module and the controller.
Flashes green
Standby:
The 3RW5 soft starter is not configured.
The 3RW5 communication module is not parameterized.
Lights up red
Irreversible error
Error can only be acknowledged by switching the control supply voltage
off and on again.
Flashes red
Reversible error (e.g. loss of the IP address due to an address conflict)
Firmware update
Off
No supply voltage available.
"BUS" LED
State
Meaning
Lights up green
At least one CIP connection and no timeout of the exclusive owner
connection.
Flashes green
An IP address is configured.
No CIP connection
Lights up red
IP address conflict
Firmware update
Flashes red
Timeout of an exclusive owner connection:
Control was stopped without connection termination.
Interruption of the Ethernet communication.
Off
Device has not yet received an IP address.
No supply voltage available.