Appendix
A.9 Dataset Object
SIRIUS 3RW5 EtherNet/IP communication module
84 Manual, 05/2019, A5E45131885002A/RS-AA/001
A.9.1 Soft starter diagnostics
Only read access (get, r) to the soft starter diagnostics is possible.
The instance of all soft starter diagnostics is 92 (0x5C).
Note
Message type of the soft starter diagnostics
In the "Soft starter diagnostics" data table, diagnostic messages may be present twice. In
this case, the message type (error (ER), warning (MT) or other message type (-)) determines
which bit is activated.
Byte Bit Attribute ID
[byte]
Data format Soft starter diagnostics 3RW Type
3)
52
1)
55
2)
0 0 301
[0 ... 1]
BOOL Ready (automatic) r r -
1 BOOL Motor CW r r -
2 BOOL Motor CCW - r -
3 BOOL Switching element overload r r ER
4 BOOL Switching element defective r r ER
5 BOOL Emergency start active - r -
6 BOOL Group error r r -
7 BOOL Group warning r r -
1 1 BOOL No supply voltage r r ER
3 BOOL Start mode active r r -
4 BOOL Stop mode active r r -
6 BOOL Electrical braking active - r -
7 BOOL Creep speed active - r -
2 0 303
[2]
BOOL Bus error r r ER
1 BOOL CPU/Master STOP r r -
2 BOOL Automatic mode r r -
3 BOOL Operating mode manual - bus r r -
4 BOOL Manual operation local r r -
6 BOOL Connection abort in manual mode r r MT
7 BOOL Error process image - r ER