Safety, approvals, EMC
7.3 EMC
SITOP expansion modules
102 Equipment Manual, 09.2022, A5E36605235-2-76
7.3 EMC
7.3.1 SITOP RED1200
6EP4346-7RB00-0AX0
6EP4347-7RB00-0AX0
6EP4348-7RB00-0AX0
6EP4347-7RC00-0AX0
Electrostatic discharge
EN 61000-4-2
8 kV contact, 8 kV air
High-speed transient disturb-
ance variables
(burst)
EN 61000-4-4
2 kV at DC input
2 kV at DC output
Surge voltages
EN 61000-4-5
0.5 kV asymmetrical on DC output cables
Generic standards
EN 61000-6-2
Interference immunity for industrial environments (only for tests appli-
cable for the device)
7.3.2 PSE202U
6EP1961-3BA21
6EP1962-2BA00
6EP1964-2BA00
Electrostatic discharge
EN 61000-4-2
4 kV contact
6 kV contact, 8 kV air
Electromagnetic fields
EN 61000-4-3
30 - 2000 MHz 3 V/m
80 - 6000 MHz 10 V/m,
1000 - 2700 MHz 10 V/m
High-speed transient disturb-
ance variables
(burst)
EN 61000-4-4 1 kV at the DC output
1 kV on the signal cable
2 kV at the DC input
2 kV at the DC output
2 kV on the signal cable
Surge voltages
EN 61000-4-5
1 kV at the DC output
1 kV on the signal cable
High-frequency fields
EN 61000-4-6
3 V; 0.15 - 80 MHz
10 V; 0.15 - 80 MHz
Magnetic fields
EN 61000-4-8
30 A/m; 50 Hz
30 A/m; 50 Hz
Emitted interference
EN 55022
(corresponds to
EN 55032)
Class B
-
Generic standards
EN 61000-6-2
-
Noise immunity for industrial
environments
EN 61000-6-3 - Interference emission for residen-
tial areas