SITOP expansion modules
Equipment Manual, 09.2022, A5E36605235-2-76
105
Ambient conditions
8
6EP4346-7RB00-0AX0
6EP4347-7RB00-0AX0
6EP4348-7RB00-0AX0
6EP4347-7RC00-0AX0
6EP4231-7HB00-0AX0
6EP4231-7HC00-0AX0
6EP1961-3BA01
6EP1961-3BA21
6EP1967-2AA00
6EP4683-6LB00-0AY0 6EP1962-2BA00
6EP1964-2BA00
Ambient temperature
-40 70 °C for natural
convection (self con-
vection)
-25 ... 60 °C for natural
convection (self con-
vection)
-40 70 °C for natural
convection (self con-
vection)
-20 70 °C for natural
convection (self con-
vection)
Tested according to:
EN 60068-2-1 Cold
EN 60068-2-2 Dry heat
EN 60068-2-78 Humid heat, constant
EN 60068-2-14 Temperature change
Transport and storage
temperature
-40 ... 85 °C
Tests (packed for shipping) according to:
EN 60068-2-1 Cold
EN 60068-2-2 Dry heat
EN 60068-2-30 Humid heat, cyclic
Humidity class
Climatic class 3K3 according to EN 60721, 5 - 95 % no condensation
Degree of pollution
2
Mechanical stressing in
operation
Tested according to EN 60068-2-6 vibration, test Fc:
3.5 mm deflection in the range 5 - 8.4 Hz
2 g acceleration in the range 8.4 - 150 Hz
3.5 mm deflection in
the range 5 - 8.4 Hz
1.3 g acceleration in
the range 8.450 Hz
Tested according to EN 60068-2-27 shock, test Ea:
acceleration 150 m/s
2
, test duration 11 ms