Technical data
6.2 Output
SITOP expansion modules
Equipment Manual, 09.2022, A5E36605235-2-76
91
6.2.3 Inrush current limiter
6EP4683-6LB00-0AY0
6EP1967-2AA00
Output
corresponding to the supply voltage
Rated output voltage Uout rated
corresponding to the supply voltage
Can be connected in parallel to
increase the power rating
No
Maximum operating current
5 A
10 A
Limiting value starting current
Approx. 10 A at 230 V AC
Approx. 8 A at 230 V AC
Recommended device combina-
tions
All SITOP power supplies
Several power supplies con-
nected in parallel at an inrush
current limiter, 1/2 phase line
supply (100 - 230 V AC)
A parallel connection is permissible. It is not
permissible that the sum of the maximum
operating currents of all of the connected
loads exceeds 5 A. The permitted switching
frequency is limited to 2 events per minute;
whereby, once per hour for the duration of
one minute an increased switching frequen-
cy is permissible (typically, 30 events per
minute). The internal temperature protec-
tion may respond if this is not complied
with.
A parallel connection is permissible. It is
not permissible that the sum of the maxi-
mum operating currents of the power
supplies exceed 10 A.
2/3 phase line supply
(400 - 480 V AC) (3 ph: observe
the wiring notes)
-
A parallel connection is permissible. It is
not permissible that the sum of the maxi-
mum operating currents of the power
supplies exceed 10 A. The permitted
switching frequency is limited to 1 event
per minute. (The internal temperature
protection may respond if this is not com-
plied with)