Description, device design, dimension drawing
2.1 Device description
SITOP expansion modules
Equipment Manual, 09.2022, A5E36605235-2-76
23
2.1.3 Inrush current limiter
2.1.3.1 Logo! ICL230
The Logo! ICL230 inrush current limiter is used to reliably reduce inrush currents, e.g. caused
by LEDs, transformers or switched-mode power supplies as a result of the rectifier circuit at
the input with capacitor charging.
It is used for 1-phase AC line supplies with 100 V, 120 V or 230 V or for 2-phase line supplies
with 208 V rated voltage on the line side, upstream of transformers, power supplies or LEDs.
Using the integrated fixed resistor, it limits the inrush current to approx. 10 A at 230 V. In
steady-state operation, the limiting resistor is bypassed after approx. 60 ms, therefore
minimizing the associated power loss.
AC input
AC output
Indicator light
Mounting rail slider
Mounting lug to remove
Convection
Clearance above/below
Figure 2-7 Design