Technical data
6.2 Output
SITOP expansion modules
90 Equipment Manual, 09.2022, A5E36605235-2-76
SITOP PSE201U
Output current (rated value)
Buffer time:
for 40 A load current: 200 ms
for 20 A load current: 400 ms
for 10 A load current: 800 ms
for 5 A load current: 1.6 s
When using 6EP1437-3BA10 the buffer time is reduced by 100 ms.
A longer buffer time is achieved for lower load currents. The maximum possible buffer time is
10 seconds.
Figure 6-1 Buffer capacity 6EP1961-3BA01