Connecting
5.4 Sensor wiring
FSS200 clamp-on sensors
Installation Manual, 08/2017, A5E36255466-AC
57
Table 5- 1 Temperature sensors
Submersible clamp-on RTD 7ME39501TB00
Standard clamp-on RTD pair for energy system
Insertion style RTD (size 1): 140 mm (5.5 in)
Insertion style RTD (size 2): 216 mm (8.5 in)
Insertion style RTD (size 3): 292 mm (11.5 in)
Insertion style RTD (size 4): 368 mm (14.5 in)
Insertion style RTD pair (size 1), 140 mm (5.5 in)
Insertion style RTD pair (size 2), 216 mm (8.5 in)
Insertion style RTD pair (size 4), 368 mm (14.5 in)
Clamp-on temperature sensors (RTDs)
Note
RTD temperature sensors are for the FST030 only.
Clamp-on style temperature sensors are mounted on the surface of the monitored pipe using
mounting assemblies. Apply a generous quantity of the thermal couplant provided to the tip
of the sensor and attach it securely to the cleaned pipe surface with the proper mounting
assembly. Temperature measurement anomalies resulting from variations in the ambient
conditions can be minimized by insulating the pipe and sensor after installation.