6 OPERATION
54
SITRANS FX300
www.siemens.com/flow 06/2009 - SFIDK.PS.050.F2.02 A5E02100423
6.5.7 Menu item Setup (firmware version - steam)
Level Designation Selection / entry Explanation
3.1 Set display
3.1.1 Error Msg.
Display error
Yes ... Shows error messages in measuring mode in plain text
alternating with the measured values
No ...^ Flashing cursor in the top left corner of the display
indicates errors.
3.1.2 Cycle.Disp.
Display measured values
Yes ... Cyclically display measured values in measuring mode
(6 s intervals)
No ...^ Do not display measured values cyclically
3.1.3 Code 1
Set security query 1 (menu)
Yes ... Activate access code:
→→→↑↑↑^^^
No ...^ Deactivate access code
3.2 I/O settings
3.2.1 4-20mA off
Current output 4-20 mA and error current
4-20mA ... Current output 4-20 mA
4-20/22E ... Current output 4-20 mA or error current 22 mA
4-20/3.55E ...^ Current output 4-20 mA or error current 3.55 mA
3.2.2 Variable I
(available if Meter Type =
Gross Heat, see menu
item 5.4.1, service menu)
Set output variable for current output
Maes.Inst ... Flow rate
Power ...^ Power
3.2.3 Power Unit
(available if Meter Type =
Gross Heat, see menu
item 5.4.1, service menu)
Set unit for heat output
kJ/h
Unit ...^
Select unit for measuring heat output
Disp. on /
Disp. off ...^
Display measured value/
Do not display measured value
3.2.4 FS power
(available if Variable I =
Power, see menu item
3.2.2)
End value for power measuring range
7000000.00
kJ/h ^
Power value at 20 mA current output
3.2.5 Function P
Function P
Yes ... Activate pulse output
No ...^ Deactivate pulse output
3.2.6 Variable P
(available if Meter Type =
Gross Heat, see menu
item 5.4.1, service menu)
Set output variable for the pulse output
Total Flow ... Total flow
Energy ...^ Energy
3.2.7 Totalizer
Totalizer
Tot. on ... Start totalizer
Tot. off ...^ Stop totalizer (value is held)
3.2.8 Tot. Conf.
Configure totalizer
MA_Siemens_Sitrans_FX300_R02_en_PRT.book Page 54 Monday, June 22, 2009 8:17 AM