7ML19985AN02 SITRANS LU10 – INSTRUCTION MANUAL Page 13
mmmmm
Installation
Connect the peripherals used, in a serial loop as follows:
Level System Synchronization
Avoid mounting the SITRANS LU10 near another ultrasonic level monitor. Likewise, when
more than one monitor is installed within a single plant / facility, ensure the transducer
cables of each system are run in separate grounded metal conduits. If this system
separation is impractical, or despite separation efforts measurement difficulties are
encountered, system synchronization may be required.
To synchronize the SITRANS LU10 with a SITRANS LU 02 or another SITRANS LU10
perform the following steps.
1. Mount the level monitors together in one cabinet.
2. Ensure the level monitors share a common power (mains) supply, and ground
(earth).
3. Interconnect the SYNC terminals of the level monitors to be synchronized.
To synchronize the SITRANS LU10 with other Siemens Milltronics ultrasonic level
To synchronize the SITRANS LU10 with other Siemens Milltronics ultrasonic level To synchronize the SITRANS LU10 with other Siemens Milltronics ultrasonic level
To synchronize the SITRANS LU10 with other Siemens Milltronics ultrasonic level
monitors (not listed) contact Siemens Milltronics or your local distributor.
monitors (not listed) contact Siemens Milltronics or your local distributor.monitors (not listed) contact Siemens Milltronics or your local distributor.
monitors (not listed) contact Siemens Milltronics or your local distributor.
Use Belden 8760 (or equivalent) 18 AWG, 2 wire shielded / twisted, 3000 m (10,000 ft) total loop length.