Installing/mounting
5
5.1 Installation instructions SITRANS CC220
Note
In󹪞uences on data transmission
The positioning of the sensors and the gateway as well as the environmental conditions
in󹪞uence the data transmission between SITRANS MS200 and SITRANS CC220. In case of an
unfavorable constellation, transmission losses may occur.
5.1.1 Mounting SITRANS CC220
Introduction
Observe the safety notes in chapter Notes on use (Page 16).
The device is approved for indoor operation only.
Install the device in cabinets, separate rooms or controlled areas. Only authorized personnel
may access the device using locks or similar measures.
Observe the relevant DIN/VDE requirements or the applicable country-speci󹪝c regulations.
Install the bluetooth antenna outside the cabinet.
To install the mounting clamps and brackets, Siemens recommends you use 0.6 Nm
tightening torque.
Before mounting the device
You have all needed anchors and screws available.
Material Bore diameter Fixing element
Concrete Select according to the speci󹪝‐
cation of the mounting ele‐
ments used
Anchor, ∅ 6 mm, 40 mm long
Screw, ∅ 4.5 mm, 40 mm long
Plasterboard,
(at least 13 mm thick)
Toggle plug, ∅ 12 mm, 50 mm long
Metal,
(at least 2 mm thick)
Screw M4 × 15
M4 nut