NOTICE
Condensation in the device
Damage to device through formation of condensation if the temperature di󹪜erence between
transportation or storage and the mounting location exceeds 20 °C (36 °F).
Before taking the device into operation, let the device adapt for several hours in the new
environment.
6.1.1 Improvement of interference immunity
Note
Improvement of interference immunity
Lay signal cables separate from cables with voltages > 60 V.
Use cables with twisted wires.
Keep device and cables at a distance from strong electromagnetic 󹪝elds.
Take account of the conditions for communication speci󹪝ed in the Technical speci󹪝cations
SITRANS CC220 (Page 69).
Use ethernet cables cat 5e/cat 6 to guarantee the full speci󹪝cation according to IEC11801
rated for 70 °C.
6.2 Connecting SITRANS CC220
Before connecting the device
You are using the supplied terminal plug.
A two-core cable meet the following requirements:
a copper (Cu) cable with cross-section of 0.75 to 2.5 mm
2
rated temperature 70 °C
A slotted screwdriver with a 3 mm blade.
Connecting SITRANS CC220
6.2 Connecting SITRANS CC220
Smart Condition Monitoring with IIoT Sensors
34 Operating Instructions, 08/2021, A5E50573389-AA