SIVACON S8 Planning Principles – Further planning notes
Environmental
conditions
Class
Environmental parameters including their limit values
(Definition acc. to IEC 60721-3-3)
Measures
Chemically
active
substances
3C2
Sea salt Presence of salt mist
on request
Mean value Limiting value
Sulphur dioxide SO
2
0.3 mg/m
3
1.0 mg/m
3
Hydrogen sulphide H
2
S 0.1 mg/m
3
0.5 mg/m
3
Chlorine Cl
2
0.1 mg/m
3
0.3 mg/m
3
Hydrogen chloride HCl 0.1 mg/m
3
0.5 mg/m
3
Hydrogen fluoride 0.01 mg/m
3
0.03 mg/m
3
Ammonia NH
3
1.0 mg/m
3
3.0 mg/m
3
Ozone O
3
0.05 mg/m
3
0.1 mg/m
3
Nitrogen oxides NO
x
0.5 mg/m
3
1.0 mg/m
3
Additional
climatic
environmental
conditions
3Z1 Heat radiation is negligible
3Z7 Dripping water in accordance with IEC 60068-2-18 IPX1
3Z9 Splashing water in accordance with IEC 60068-2-18 IPX4
3B2
Flora Presence of mould, fungus, etc.
≥ IP4X including
protection of the
cable basement
Fauna
Presence of rodents and other animals
harmful to products, excluding termites
Mechanically
active
substances
3S1
Sand in air -
< IP5XDust (suspension) 0.01 mg/m
3
Dust (sedimentation) 0.4 mg/(m
3
∙h)
3S2
Sand in air 300 mg/m
3
≥ IP5XDust (suspension) 0.4 mg/m
3
Dust (sedimentation) 15 mg/(m
3
∙h)
Conditions for transport, storage and installation
If the ambient conditions for transport, storage or switch-
board installation deviate from the normal service condi-
tions listed in Tab. 8/4 (for example an excessively low or
high value for temperature or air humidity), the measures
required for proper treatment of the switchboard must be
agreed upon between manufacturer and client.
Tab. 8/4: Special service conditions for SIVACON S8 switchboards