If hardware fail flashing is available
HPU Relays switch
off LSLS cards:
A:LSLS 1 On
B:LSLS 1 On
FailFlash Available
But Not Selected.
Switches each LSLS output on in turn
(Amber LED moves across all LSLS
cards) to check that all outputs are
working.
Relay A Control by Primary CPU Test
LSLS output test continues
Relay B Control by SEC CPU Test
LSLS output test continues
LSLS Outputs:21-xx
LSLS Outputs:Passed
1st pass of self test complete.
After a short period the second stage of
the test is repeated indefinitely to allow
the controller to be soak tested if
required.
==================
Pass 0001 Complete
==================
11.5.1 Test Failures
If test fail during the 1st part of self test the handset output will provide details of the
failure. The section below details the output and describes what possible causes
there are.
M/V Test.....Failed
Mon Val Failed
The monitor validation signal is generated by the CPU Card and travels down the
phase bus cables to each of the LSLS cards, so a failure is probably due to a faulty
LSLS Card or interconnecting cable. If two lamp supply transforms are used, check
the live-neutral connections to those are correct and consistent. If, after checking
and/or replacing these items, the problem persists, there is the possibility that the
logic supply phasing may be incorrect – contact Siemens Engineering in Poole for
further information.
V/Mons Off...Failed
100000000 4--------
200000001 5--------
3-------- 6--------