9.2.9.4 Settings
Path: … > COMMIS > CONF > CTLOOP 1
Configuration
Display Name Range / comments
STRATGY Control strategy LIM
Path: … > PARA > CTLOOP 1
Setting values
Display Name Range Factory setting
LIM MAX Gen limiter limit
value high
Input range
limit sensor
35 °C
LIM MIN Gen limiter limit
value low
Input range
limit sensor
16 °C
LIM DHI Gen limiter
differential high
0…500 K 50 K
LIM DLO Gen limiter
differential low
0…500 K 50 K
LIMCOOL Reduction min
limitation cooling
0…10 K 0 K
LIM XP Gen limiter P-band
Xp
0…500 K 15 K
LIM TN Gen limiter integr
action time Tn
00.00…60.00 m.s 02.00 m.s
104 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Controller (CTLOOP x) 29.08.2008