14.5 Modulating / 2-position converter
Switch-on and switch-off command (at Q1) according to the resistance signal from
an LG-Ni1000 passive temperature sensor (at X1): ON at 28 °C, OFF at 25 °C.
Purpose
CONF / X1 / LABEL %
Configuration
CONF / X1 / SIGNALY ---
CONF / STEP V1 / STEP 1 Q1
CONF / STEP V1 / IN X X1
PARA / D1 / NORMPOS OPEN
Setting values
PARA / X1 / MIN VAL 0 %
PARA / X1 / MIN VAL 100 %
PARA / STEP V1 / OFFTIME 00.00
PARA / STEP V1 / S1-ON 28 %
PARA / STEP V1 / S1-OFF 25 %
14.6 Signal doubler
You want to transmit a DC 0…10 V signal (at X1) as an active output (at Y1).
Purpose
CONF / X1 / LABEL %
Configuration
CONF / X1 / SIGNALY Y1