9.10 Universal setpoint shift
9.10.1 Activation
Universal setpoint shift is available with:
Controller 1,
basic type U,
controller 2
• Controller 1, basic type U only
• Controller 2
To activate the function, configure an appropriate input. You can only assign analog
inputs.
9.10.2 Operating principle
You can use a universal input to shift the controller's setpoint.
Function
Setpoint shift acts on the Comfort and Economy modes according to the following
diagram:
Diagram
3101D09
SETCOOL
SETHEAT
Δ
w
[K]
AI
w
CMP1END CMP2ENDCMP1STT CMP2STT
CMP2D
CMP1D
AI
Legend:
AI Analog input
w Setpoint
Δw Setpoint shift
Typical applications for universal setpoint shift are:
Application
• Refrigeration: Shifting the flow temperature setpoint for the chilled ceiling
according to room enthalpy or surface temperature
• Ventilation: Shifting according to room humidity or surface temperature
9.10.3 Troubleshooting
When you leave the commissioning menu, the universal controller checks whether
a sensor is connected.
Sensor connected?
• If, at that time, a sensor is connected, but is missing later, a sensor error
message is delivered and presented on the display:
– "Xx ---" => sensor missing
– "Xx ooo" => short-circuit
• If, at that time, the sensor is not connected, setpoint compensation will be
deactivated
131 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Controller (CTLOOP x) 29.08.2008