9.10.4 Settings
Path: … > COMMIS > CONFIG > CTLOOP 1
Configuration
… > COMMIS > CONFIG > CTLOOP 2
Display Name Range / comments
SHIFT Universal shift Adjustable values:
---, X1, X2, … (analog values only)
Path: … > PARA > CTLOOP 1
Setting values
… > PARA > CTLOOP 2
Display Name Range Factory
setting
CMP2D [Setp compensation 2]
delta
50…+500 K 0 K
CMP2END [Setp compensation 2] end CMP2STT…500 °C 30 °C
CMP2STT [Setp compensation 2]
start
CMP1STT
…CMP2END
20 °C
CMP1STT [Setp compensation 1]
start
CMP1END...
CMP2STT
0 °C
CMP1END
...
[Setp compensation 1] end 50 °C… CMP1STT 10 °C
CMP1D [Setp compensation 1]
delta
50…+500 K 0 K
132 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Controller (CTLOOP x) 29.08.2008