EasyManua.ls Logo

Siemens Synco 200 - Wiring test

Siemens Synco 200
174 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4.5 Wiring test
When the peripheral equipment is connected, you can perform a wiring test in the
TEST (wiring test) menu. We recommend testing after configuration and settings
are complete. The test provides the following functions:
Functions
Display of reading values for inputs
Switching of aggregates connected to the outputs, such as pumps
Preselection of a 0…100% signal for step switches, where the relays are
switched
The application is deactivated during the wiring test. The outputs are in a defined
OFF state, and safety-related functions (e.g. frost protection) are deactivated!
The wiring test provides checks for the following errors at the inputs and outputs:
Error checks
Connection error (mixed up wires)
Position error (mixed up sensors or actuating devices)
Discrepancies between connection method and controller configuration (LG-
Ni1000 in place of active DC 0…10 V)
28 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Commissioning 29.08.2008

Table of Contents

Other manuals for Siemens Synco 200

Related product manuals