9.9 Summer / winter compensation
9.9.1 Activation
Summer / winter compensation is only activated for controller 1, basic type A.
Controller 1, basic
type A
It is always active if an outside temperature signal is available.
9.9.2 Operating principle
This function shifts the room temperature controller's setpoint as a function of the
outside temperature.
Function
This setpoint shift acts on the Comfort and Economy modes according to the
following diagram:
Diagram
w
Δ
w
[K]
SUM-END
SUM-STTWIN-END WIN-STT
SETCOOL
SETCOOL
SETHEAT
SETHEAT
SUM-D
WIN-D
3101D08de
TA
TA
Legend:
WIN-D Winter comp. delta
SUM-D Summer comp. delta
WIN-END Winter comp. end point
WIN-STT Winter comp. starting point
SUM-STT Summer comp. starting point
SUM-END Summer comp. end point
OT Outside temperature
w Setpoint
Δw Setpoint shift
Upward shift at low outside temperatures acts on heating and cooling
Explanations for the
diagram
Downward shift at low outside temperatures acts on heating
Upward shift at high outside temperatures acts on cooling
Downward shift at high outside temperatures acts on heating and cooling
The purpose of summer / winter compensation is as follows:
Application
Summer compensation to compensate for the lighter clothing worn by building
occupants
Winter compensation to compensate for cold surfaces in the room, such as the
windows