7.3 Digital inputs (D1, D2, X1…X5)
Signals for open-loop control functions (e.g. mode selector switch) can be
connected to the digital inputs. There are 2 types of digital input:
Purpose and types
Permanently assigned digital inputs D1 and D2
Universal inputs X1…X5, activated as digital inputs X1…X5
For each digital input, the normal position can be predefined.
Normal position
The following positions can be selected: Open / Closed (OPEN / CLSD)
Only potential-free contacts can be connected to the digital inputs.
Connection diagram
G
G
G0
X...
G0
N
3101A13
AC 24 V
M
F...
Δ
p
X... M
F...
The digital signals cannot be monitored. If an important protection function, such as
a frost protection unit, is connected to this input, we recommend that you make the
wiring in such a way that a frost alarm is also triggered if there is no signal (cable
break). Setting value ”Normal position”: Closed
Troubleshooting
44 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Inputs 29.08.2008