14.3 Signal adaptation
You want to adapt a DC 0…10 V signal (at X1) to DC 5…7.5 V (at Y1).
Purpose
CONF / X1 / LABEL %
Configuration
CONF / X1 / SIGNALY ---
CONF / AO 1 / AO Y1
CONF / AO 1 / IN X X1
PARA / D1 / NORMPOS OPEN
Setting values
PARA / AO 1 / MIN POS 50 %
PARA / AO 1 / MAX POS 75 %
PARA / AO 1 / INVERS NO
14.4 Step switch
You want to convert a DC 0…10 V signal (at X1) and an enable signal (at D1) to a
binary step switch signal with 2 steps (at Q1+Q2).
Purpose
CONF / X1 / LABEL %
Configuration
CONF / X1 / SIGNALY ---
CONF / STEPBIN / STEP 1 Q1
CONF / STEPBIN / STEP2 Q2
CONF / STEPBIN / IN X X1
PARA / D1 / NORMPOS CLSD
Setting values
PARA / STEPBIN / OFFTIME 00.00