Path: … > PARA > CTLOOP 1
Setting values
… > PARA > CTLOOP 2
Display Name Range Factory setting
SEQ1 XP [Sequence 1 \_ ] Xp 0…500 K 30 K
SEQ1 TN [Sequence 1 \_ ] Tn 00.00…60.00 m.s 03.00 m.s
SEQ1 TV [Sequence 1 \_ ] Tv 00.00…60.00 m.s 00.00 m.s
SEQ2 XP [Sequence 2 \ .._ ] Xp 0…500 K 30 K
SEQ2 TN [Sequence 2 \ .._ ] Tn 00.00…60.00 m.s 03.00 m.s
SEQ2 TV [Sequence 2 \ .._ ] Tv 00.00…60.00 m.s 00.00 m.s
SEQ4 XP [Sequence 4 _/ ] Xp 0…500 K 30 K
SEQ4 TN [Sequence 4 _/ ] Tn 00.00…60.00 m.s 03.00 m.s
SEQ4 TV [Sequence 4 _/ ] Tv 00.00…60.00 m.s 00.00 m.s
SEQ5 XP [Sequence 5 _.. / ] Xp 0…500 K 30 K
SEQ5 TN [Sequence 5 _.. / ] Tn 00.00…60.00 m.s 03.00 m.s
SEQ5 TV [Sequence 5 _.. / ] Tv 00.00…60.00 m.s 00.00 m.s
TIMEOUT Control timeout 00.00…60.00 m.s 00.00 m.s
Path: INFO
Display values
Display Name Comments
\_ [Sequence 1] load output Indication of sequence controller's
present output as 0…100% with a
sequence diagram and controller icon
\ \_ [Sequence 2] load output See comment above
_/ [Sequence 4] load output See comment above
_/ / [Sequence 5] load output See comment above
Inverted sequences are also shown inverted, e.g. [Sequence 1] load output analog
output is inverted: /_
120 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Controller (CTLOOP x) 29.08.2008