Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Appendix 29.08.2008
Aggregates
(cont’d)
STEP Vx (variable
step switch)
Configuration Functions
y1 y2 x
QQQQQQ Y
IN X
S
T
E
P
1
S
T
E
P
2
S
T
E
P
3
S
T
E
P
4
S
T
E
P
5
S
T
E
P
6
AO
STEP V2
Step 1 to … (STEP x)
Modulating output (AO)
External signal (IN X)
For controlling a multistage aggregate.
A switch-on and switch-off point can be assigned to each step
according to the load signal from the sequence controller (from up to
2 sequences with maximum selection) The switching points can
overlap and can be inverted (ON < OFF)
External load signal can be applied
Configurable modulating output. Same function as modulating outputs
AO x
Locking time (restart delay) is adjustable (time applies to all steps)
STEP LIN (linear step
switch)
Configuration Functions
y1 y2 x
QQQQQQ Y
IN X
S
T
E
P
2
S
T
E
P
3
S
T
E
P
4
S
T
E
P
5
S
T
E
P
6
AO
S
T
E
P
1
STEP LIN
Step 1 to … (STEP x)
Modulating output (AO)
“External preselection” input (IN
X)
For controlling a multistage aggregate.
Linear distribution of the steps over the load signal range according to
the number of outputs assigned
External load signal can be applied
Modulating output can be configured, same function as modulating
outputs AO x
Locking time (restart delay) and startup delay time are adjustable
(time applies to all steps)
Weekly priority changeover of the steps
STEB BIN (binary
step switch)
Configuration Functions
y1 y2 x
QQQQ Y
IN X
S
T
E
P
2
S
T
E
P
3
S
T
E
P
4
S
T
E
P
1
AO
STEP BIN
Step 1 to … (STEP x)
Modulating output (AO)
“External preselection” input (IN
X)
For controlling a multistage aggregate.
Binary distribution of the steps over the load signal range according to
the number of outputs assigned
External load signal can be applied
Modulating output can be configured, same function as modulating
outputs AO x
Locking time (restart delay) is adjustable (time applies to all steps)
3P (3-position) Configuration Functions
y1 y2
IN X
x
Q1 Q2
OPEN
CLOSE
3 P
3 POINT
3-position output (3-POINT)
“External preselection” input (IN
X)
For controlling a 3-position actuator.
End stop synchronization
External load signal can be applied
Actuator running time adjustable