8.1.6 Settings
Path: … > COMMIS > CONF > PUMP 1
Configuration
… > COMMIS > CONF > PUMP 2
… > COMMIS > CONF > PUMP 3
Display Name Range / comments
PUMP x Output Output of pump x (1, 2, 3) to a relay;
adjustable values: ---, Q1, Q2, … (free
outputs only)
Path: … > PARA > PUMP 1
Setting values
… > PARA > PUMP 2
… > PARA > PUMP 3
Display Name Range Factory setting
Y ON Load-dependent ON 0…100 % 5 %
OFF-Y Load-dependent OFF 0…100 % 0 %
ON-OUTS Outside temp-dependent
ON
−50…+250 °C −50 °C
DLY OFF Switch-off delay 00.00…60.00 m.s 00.00
KICK Kick period 0…200h 0
Path: INFO
Display values
Display Name Comments
PUMP 1 Pump 1 Indication of current state: Off, On…
PUMP 2 Pump 2 Indication of current state: Off, On…
PUMP 3 Pump 3 Indication of current state: Off, On…
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
PUMP 1 Pump 1 Off, On…
PUMP 2 Pump 2 Off, On…
PUMP 3 Pump 3 Off, On…
57 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Aggregates 29.08.2008