8.2.4 Wiring test (TEST)
During the wiring test, the modulating output can be directly commanded via the
control switch.
Switching on / off
The switch has the following positions:
Switch positions
• ---
• 0…100% load
Settings such as INVERS, MIN POS and MAX POS are also effective during the
wiring test.
Note
8.2.5 Settings
Path: … > COMMIS > CONF > AO 1
Configuration
… > COMMIS > CONF > AO 2
… > COMMIS > CONF > AO 3
Display Name Range / comments
AO x Modulating output Activation of modulating output; adjustable
values: ---,Y1, Y2, Y3
IN X Preselection
external
Adjustable values: ---, X1, X2, … (inputs
with identifier % only)
Path: … > PARA > AO 1
Setting values
… > PARA > AO 2
… > PARA > AO 3
Display Name Range Factory setting
MIN POS Positioning signal min 0…100 % 0 %
MAX POS Positioning signal max 0…100 % 100 %
INVERS Inversion NO, YES NO
ON-OUTS Outside temp-dependent ON −50…+250 °C −50 °C
%OPEN Outside temp-dependent open 0…100 % 0 %
Path: INFO
Display values
Display Name Comments
AO 1 Modulating output 1 0…100 %
AO 2 Modulating output 2 0…100 %
AO 3 Modulating output 3 0…100 %
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
AO 1 Modulating output 1 ---, 0…100 %
AO 2 Modulating output 2 ---, 0…100 %
AO 3 Modulating output 3 ---, 0…100 %
61 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Aggregates 29.08.2008