8.3.11 Settings
Path: … > COMMIS > CONF > HREC
Configuration
Display Name Range / comments
HREC Mixing damper/HR Activation of HR; adjustable values: ---, Y1,
Y2, …
MECH 1 MECH input 1 Adjustable values: ---, X1, X2, … (only °C,
0.0, 0000, digital)
MECH 2 MECH input 2 Adjustable values: ---, X1, X2, … (only °C,
0.0, 0000)
MAT Mixed air temperature Adjustable values: ---, X1, X2, … (only °C,
0.0, 0000)
IN X Preselection external Adjustable values: ---, X1, X2, … (inputs
with identifier % only)
COOLER Cooling coil valve ---, AO1, AO2, AO3, STP1, STP2, STP3,
SLIN, SBIN, 3P
Path: … > PARA > HREC
Setting values
Display Name Range Factory setting
TYPE Type ERC, DMP ERC
MIN POS Positioning signal min 0…100 % 0 %
MAX POS Positioning signal max 0…100 % 100 %
MECHSET MECH limit value 3 K, 20 °C
STUP-TI Startup time 00.00...60.00 m.s 00.00 m.s
MAT SP Mixed air temperature
setpoint
-50 °C … 250 °C
12 °C
MAT XP
Mixed air temp P-band Xp
0.0 ... 500 K
10 K
MAT TN
Mixed air temp int act time Tn 00.00...60.00 m.s 02.00 m.s
Path: INFO
Display values
Display Name Comments
HREC Mixing damper/HR 0…100 %
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
HREC Mixing damper/HR ---, 0…100 %
74 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Aggregates 29.08.2008