8.6.6 Settings
Path: … > COMMIS > CONF > STEPBIN
Configuration
Display Name Range / comments
STEP 1 Step 1 Activation of step switch and selection of the
number of steps; adjustable values:---, Q1, Q2,
… (free outputs only)
STEP 2 Step 2 ---, Q1, Q2, … (free outputs only)
STEP 3 Step 3 ---, Q1, Q2, … (free outputs only)
STEP 4 Speed 4. ---, Q1, Q2, … (free outputs only)
AO Modulating
output
---, Y1, Y2, … (free outputs only)
IN X Preselection
external
---, X1, X2, … (inputs with identifier % only)
Path: … > PARA > STEPBIN
Setting values
Display Name Range Factory setting
OFFTIME Locking time 00.00…10.00 m.s 00.00
MIN POS Positioning signal min 0…100 % 0 %
MAX POS Positioning signal max 0…100 % 100 %
INVERS Inversion NO, YES NO
Path: INFO
Display values
Display Name Comments
STEPBIN Binary step switch 0…100%
STEP x Binary step switch, step x ON, OFF
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
STEPBIN Binary step switch ---, 0…100 %
STEP x Binary step switch, step x ON, OFF
87 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Aggregates 29.08.2008