8.7.6 Settings
Path: … > COMMIS > CONF > 3-POINT
Configuration
Display Name Range / comments
3P 3-position Activation of 3-position output function;
adjustable values: NO, YES
IN X Preselection
external
---, X1, X2, … (inputs with identifier % only)
Path: … > PARA > 3-POINT
Setting values
Display Name Range Factory setting
ACTTIME Actuator running time 0.10…10.00 m.s 2.00 m.s
Path: INFO
Display values
Display Name Comments
3P 3-position 0…100 %
Path: … > COMMIS > TEST
Wiring test
Display Name Positions
3P 3-position ---, OPEN, CLOSE
90 / 174
Siemens Universal Controllers RLU2… CE1P3101en
Building Technologies Aggregates 29.08.2008