DL100 Series Universal Low-Power Inverter
28 Detailed Description of Functions
This function is used to prevent accidental modification of data.
5:Only allow to modify function parameter [F0.01] and this parameter
9:Only allow to modify this parameter
Other values: all parameters are allowed to be rewritten.
When it is forbidden to modify the parameters, if you try to modify the data, it
will display“- -”.
This parameter is the lowest frequency lower limit allowed by the inverter.
When the frequency is lower than the lower limit frequency, refer to parameter
[F0.05] for the mode of action.
0 : When lower than the lower limit frequency [F0.04], output the lower
limit frequency [F0.04]
1:Output zero frequency when it is lower than the lower limit frequency
[F0.04]
This parameter can set the hysteresis function to avoid fluctuations near the
zero point of the set frequency. When the set frequency is lower than f (f=lower
limit frequency), the inverter runs at zero frequency. Increase the set frequency.
When the set frequency is higher than the lower limit frequency, the inverter will
run at the set frequency. Its function is shown in Figure 6-1:
F0.02 Parameter write protection Setting range:0 ~ 20
Some parameters cannot be rewritten during operation. If
you try to modify these parameters at this time, "- -" will be
displayed. If you want to modify the parameters, please stop the
inverter before modifying it.
F0.04 Lower limit frequency Predetermined area
:
0.00 Hz ~ [F0.3]
F0.03 Upper limit frequency Predetermined area
:
5.00~ 600.00Hz
F0.05 Lower limit frequency action mode Predetermined area
:
0 ~ 1