DL100 Series Universal Low-Power Inverter
Detailed Description of Functions 29
This function parameter is used to select the running command channel of the
inverter, and the function of the key (decimal setting).
LED units: run command channel selection
0 Keyboard control
The inverter running command is controlled by the key on the keyboard.
In this mode, the state of the external control terminals X1~X4 (forward
running function) can affect the output phase sequence of the inverter. When the
external terminals X1~X4 (forward running function) are connected to CM, the
inverter outputs the reverse sequence; When X1~X4 are disconnected from CM,
the inverter outputs positive phase sequence.
1 External terminal control
The inverter running command is controlled by the on-off status of the
multi-function terminals X1~X4 and the CM terminal, and the mode is determined
by the LED tens.
2 Serial communication port
The running command of the inverter receives commands from the upper
computer or host computer through the serial interface. This mode should also be
selected when the machine is set as a slave in the linkage control.
F0.06 Run command channel and mode selection
Predetermined area
0000 ~ 1022
Actual set
frequency
Figure 6-1 Schematic diagram of the lower limit frequency